045488 · Installation Guide · Rev B · Jul 2016 · English, French, Spanish, Italian, Portuguese, German, Chinese · PDF, 2 pages, 3.1 MB

Lutron Sivoia QS Roller Shades Installation Guide: QS Link Plug-In Power Supply, NEMA 5-15 Plug, 120 V to 240 V Input, 35 V Output (045488, rev B)

Lutron's installation guide for the QSPS-1-35V QS Link plug-in power supply, which feeds one Sivoia QS shade or drapery drive.

About document 045488

Lutron document 045488, Rev B of July 2016, is the QSPS-1-35V plug-in power supply installation guide: wiring rules, run length by wire gauge, terminals, drive and PDU connections, daisy-chained supplies, AC cord and mounting.

What guide 045488 covers

Lutron document 045488 has these eight sections, all on page 1.

  1. Rules for QS link wiring
  2. Capacity and maximum run by wire gauge
  3. Important notes
  4. Connect the power supply
  5. Mount the power supply
  6. Input and output ratings and dimensions
  7. FCC and IC notice
  8. Customer assistance and warranty

Specifications in 045488

Lutron document 045488 prints 26 values in the groups the document uses, each with the document's unit. A row names the catalog codes it applies to. The page link beside each group opens the PDF where the group starts.

Input
120 V~ to 240 V~, 50/60 Hz, 1.2 AModels: QSPS-1-35V
Output
35 V DC, 143 mAModels: QSPS-1-35V
With 1 shade or drapery drive
Up to 1 PDUModels: QSPS-1-35V
With no shade
Up to 8 PDUsModels: QSPS-1-35V

Maximum 35 V / COM run, 1 drive and up to 1 PDU

PDF page 1 of 045488, opens in a new tab
12 AWG (4.0 mm²)
250 ft (75 m)Models: QSPS-1-35V
16 AWG (1.5 mm²)
100 ft (30 m)Models: QSPS-1-35V
18 AWG (1.0 mm²)
50 ft (15 m)Models: QSPS-1-35V

Maximum 35 V / COM run, no shade and up to 8 PDUs

PDF page 1 of 045488, opens in a new tab
12 AWG (4.0 mm²) and 16 AWG (1.5 mm²)
2000 ft (610 m)Models: QSPS-1-35V
18 AWG (1.0 mm²)
1500 ft (450 m)Models: QSPS-1-35V
Communication cable
One pair 22 AWG (0.5 mm²), twisted and shielded, for MUX and MUX
Total link wiring in the system
Not over 2000 ft (610 m)
Secondary wiring type
CL2, CL2P, CL2R, CL2X or cable with equivalent or better ratings to local and national code
+35 V between devices supplying PDUs
Never connected
Strip length
1/4 in (6 mm)Models: QSPS-1-35V
Screw torque
5 in-lb (0.5 N·m)Models: QSPS-1-35V
Connector
IEC C13Models: QSPS-1-35V
Conductors
18 AWG (1.0 mm²), 3-conductorModels: QSPS-1-35V
Rating
300 V, 140 °F (60 °C)Models: QSPS-1-35V
Length
6 ft (1.83 m) minimum, 10 ft (3 m) maximumModels: QSPS-1-35V
Outlet
Standard receptacleModels: QSPS-1-35V
Ambient operating temperature
32 °F to 104 °F (0 °C to 40 °C)Models: QSPS-1-35V
Humidity
0 to 90%, non-condensingModels: QSPS-1-35V
Location
Indoor use onlyModels: QSPS-1-35V
Method
Optional, mounting tabs with fasteners suited to the surface; hand tighten only, no power toolModels: QSPS-1-35V
Drawing values
2.75 in (70 mm), 1.25 in (32 mm), 4.0 in (103 mm)Models: QSPS-1-35V
Compliance statements
FCC part 15, Class B digital device limits; Class B digital apparatus to Canadian ICES-003 / NMB-003Models: QSPS-1-35V

Installation walk-through for 045488

Lutron document 045488 gives five steps, in the document's order, after the fixings it lists.

The clearance, the check and the warning under a step are the document's own.

Fixings

  • Power cord supplied, or an approved cord with an IEC C13 connector
  • Cord: 18 AWG (1.0 mm²) 3-conductor, 300 V, 140 °F (60 °C)
  • Cord length 6 ft (1.83 m) to 10 ft (3 m)
  • Fasteners suited to the mounting surface, through the tabs (optional)
  • One twisted, shielded pair of 22 AWG (0.5 mm²), communication link
  • Power and common conductors sized from the run length table
  • Conductor sizes: 12 AWG (4.0 mm²), 16 AWG (1.5 mm²) or 18 AWG (1.0 mm²)
  1. Mount the power supply (optional)

    Fix the supply through its mounting tabs with fasteners that suit the surface, tightened by hand.

    Lutron recommends a location that stays accessible. The supply must not interfere with the window treatment or any other moving device.

    Check: Supply reachable later and clear of the shade's travel

    Warning: Hand tighten only; no power tool on the fasteners

  2. Prepare the conductors

    Strip 1/4 in (6 mm) of insulation from each conductor. Tighten every terminal screw firmly to 5 in-lb (0.5 N·m) as each wire is landed.

    Clearance: Strip 1/4 in (6 mm); torque 5 in-lb (0.5 N·m)

    Check: No insulation inside the terminal block

  3. Connect the drive or the power draw units

    Land the power and common wires on the matching 35 V and COM terminals. In a wired control installation, land the communication wires on the matching MUX and MUX terminals.

    A wireless control installation leaves those terminals empty.

    Clearance: 35 V and COM run, one drive: 250 ft (75 m) on 12 AWG (4.0 mm²), 100 ft (30 m) on 16 AWG (1.5 mm²). On 18 AWG (1.0 mm²), 50 ft (15 m).

    Check: One drive and at most one PDU, or up to 8 PDUs with no shade

    Warning: +35 V is never connected between devices that supply power draw units

  4. Connect further supplies on the link (optional)

    Several supplies, each with its own devices, may be daisy-chained along the wired communication link. Land the incoming link wires on one side of the pass-through and the outgoing wires on the other.

    Clearance: All QS link wiring in the system not over 2000 ft (610 m)

    Check: Only the communication link joins the supplies

    Warning: No +35 V conductor runs from one supply to the next

  5. Connect the AC cord

    Use the cord supplied, or any approved cord that suits the installation site and meets the IEC C13 cord requirements. Plug the cord into the supply first, then into a standard receptacle.

    Clearance: Cord 6 ft (1.83 m) minimum, 10 ft (3 m) maximum

    Check: Cord is 18 AWG (1.0 mm²) 3-conductor, rated 300 V and 140 °F (60 °C)

Other warnings Lutron prints in 045488
  • All wiring and circuit protection must meet national and local electrical codes
  • Indoor use only, in 32 °F to 104 °F (0 °C to 40 °C)
  • 0 to 90% humidity without condensation
  • Never connect +35 V between devices that supply power draw units
  • Secondary wiring: CL2, CL2P, CL2R, CL2X, or equal or better in rating
  • Equal or better means electrical, mechanical and flammability ratings

Requirements Lutron states in 045488

What the guide requires for a Sivoia QS shade before and during installation:

Input
120 V to 240 V AC, 50/60 Hz, 1.2 A, through an AC cord plugged into a standard receptacle
Output
35 V DC, 143 mA
Capacity
One shade or drapery drive and up to 1 power draw unit (PDU). With no shade, up to 8 PDUs.
Run with one drive
Maximum 35 V and COM run with one drive:
  • 250 ft (75 m) on 12 AWG (4.0 mm²)
  • 100 ft (30 m) on 16 AWG (1.5 mm²)
  • 50 ft (15 m) on 18 AWG (1.0 mm²)
Run with PDUs only
Maximum 35 V and COM run with no shade and up to 8 PDUs. 2000 ft (610 m) on 12 AWG (4.0 mm²) or 16 AWG (1.5 mm²), and 1500 ft (450 m) on 18 AWG (1.0 mm²).
QS link communication cable
  • One twisted, shielded pair of 22 AWG (0.5 mm²) for MUX and MUX
  • Total QS link wiring in the system: not more than 2000 ft (610 m)
  • Secondary wiring CL2, CL2P, CL2R, CL2X, or an equivalent or better cable
Power rule
The +35 V conductor is never connected between devices that supply power draw units
Terminals
Strip 1/4 in (6 mm) of insulation. Tighten each terminal screw to 5 in-lb (0.5 N·m) with no insulation inside the terminal block.
Wired and wireless control
The MUX terminals carry the communication wires in a wired control installation and stay unused in a wireless control installation
Several supplies
Supplies and their devices may be daisy-chained along the wired communication link. Incoming link wires land on one side of the pass-through, outgoing wires on the other.
AC cord
  • The supplied cord or an approved equivalent
  • IEC C13 connector, 18 AWG (1.0 mm²) 3-conductor
  • Rated 300 V and 140 °F (60 °C)
  • Length 6 ft (1.83 m) minimum to 10 ft (3 m) maximum
Mounting
Optional, through the mounting tabs with fasteners suited to the surface, hand tightened only. Lutron recommends a spot that stays accessible and clear of window treatments and other moving devices.
Ambient operating environment
Indoor use only, in 32 °F to 104 °F (0 °C to 40 °C) at 0 to 90% humidity with no condensation

Questions about document 045488

The answers come from Lutron document 045488 and New Way's record of it.

What is Lutron document 045488?

Lutron's two-page QSPS-1-35V plug-in power supply installation guide, P/N 045488 revision B, dated 07/2016, in seven languages.

Which revision of 045488 is current?

Rev B, dated July 2016, is the revision Lutron publishes. New Way checked it against assets.lutron.com on 15 October 2026.

Which roller shades does 045488 cover?

Lutron Sivoia QS roller shades. Lutron document 045488 refers readers to document 369405.

How many shades can one QSPS-1-35V power?

One: Lutron document 045488 rates the QSPS-1-35V for one shade or drapery drive plus up to one power draw unit. With no shade connected, it feeds up to eight power draw units.

Lutron document 045488 gives the output as 35 V DC at 143 mA.

How far can the 35 V run go from supply to drive?

Up to 250 ft (75 m) on 12 AWG (4.0 mm²) with one drive and one PDU, per Lutron document 045488.

  • 16 AWG (1.5 mm²): up to 100 ft (30 m)
  • 18 AWG (1.0 mm²): up to 50 ft (15 m)
  • PDUs only: 2000 ft (610 m) on 12 AWG (4.0 mm²) or 16 AWG (1.5 mm²)

Can several plug-in power supplies share one QS link?

Yes: Lutron document 045488 daisy-chains several supplies and their devices along the wired communication link. Incoming wires land on one side of the pass-through terminals, outgoing on the other.

Lutron document 045488 forbids joining the +35 V conductor between devices that supply power draw units.

How are the conductors terminated at the supply?

Lutron document 045488 strips 1/4 in (6 mm) from each conductor and tightens every terminal screw to 5 in-lb (0.5 N·m). No insulation is left inside the terminal block.

Power and common land on 35 V and COM. The communication pair lands on MUX and MUX only in a wired control installation.

What cord and outlet does the supply need?

Lutron document 045488 calls for the supplied cord or an approved one, plugged into a standard receptacle.

  • IEC C13 connector, 18 AWG (1.0 mm²) 3-conductor, rated 300 V
  • Rated 140 °F (60 °C); 6 ft (1.83 m) to 10 ft (3 m) long
  • Input 120 V to 240 V AC, 50/60 Hz, 1.2 A
Ask about 045488

Other Sivoia QS installation guides

Installation guides for the same Sivoia QS system:

All 36 Sivoia QS installation guides

Documents used with 045488

Lutron documents 045604 and 045528 are the junction box supply and smart panel installation guides. Lutron document 085329 is the plug-in supply's specification submittal; 369405 is the QS link power draw unit submittal it cites.

Revisions of 045488

This page always shows the revision Lutron publishes today. Lutron replaces the file in place and does not keep earlier revisions online.

RevisionDateStatus
BJul 2016Current. The file on assets.lutron.com. Checked 15 Oct 2026.

Not covered in 045488, and what to read next

Lutron document 045488 gives no PDU value per QS device, no drive wiring at the shade and no limit setting.

  • PDU values: 369405, the QS link power draw unit specification submittal
  • Supply data: 085329, the plug-in power supply specification submittal

Publisher and citation for document 045488

Lutron Electronics Co., Inc. publishes document 045488, Rev B, and serves it from assets.lutron.com. New Way hosts no copy and last checked the file there on 15 October 2026.

Lutron and Sivoia QS are trademarks of Lutron Electronics Co., Inc.

Reviewed by Edmond Hong, Technical Specialist, New Way.

Specifying Sivoia QS?

New Way supplies and installs Lutron Sivoia QS shading in Malaysia and Singapore. A New Way specifier can check your shade schedule and drawings before you submit.

The form opens with document 045488 filled in.