Lutron document 045528 has these nine sections, all on its one page.

  1. Important notes
  2. Prepare the smart panel
  3. Mount the smart panel
  4. Connect line voltage
  5. Connect Sivoia QS window treatments or lighting devices
  6. QS link wiring rules and output capacity table
  7. Connect multiple smart panels and other QS devices
  8. Monitor, verify and diagnose operation
  9. FCC and IC notice and customer assistance

Specifications in 045528

Lutron document 045528 prints 32 values in the groups the document uses, each with the document's unit. A row names the catalog codes it applies to. The page link beside each group opens the PDF where the group starts.

Input
120 V to 240 V~, 50/60 Hz, 10 AModels: QSPS-10PNL, QSPS-10PNL-NPM
Per output
35 V DC, 143 mA, 5 WModels: QSPS-10PNL, QSPS-10PNL-NPM
Minimum feed circuit breaker
15 A, set by inrush current (16 A may suit some countries)
Maximum feed circuit breaker
20 A
Ambient operating temperature
32 °F to 104 °F (0 °C to 40 °C)
Humidity
0 to 90%, non-condensing
Use
Indoor only; not for phase-to-phase installations
Surface mount
3 keyholes; fasteners rated for a 50 lb (23 kg) load
Figure 2a (surface mount), dimensions marked
4.75 in (121 mm); 0.75 in (22 mm); 1.50 in (38 mm); 6.00 in (152 mm); 1.77 in (45 mm)
Figure 2b (recess mount), dimension marked
16.00 in (406 mm)
Feed wire
10 AWG to 14 AWG (4.0 mm² to 2.5 mm²)
Strip length
5/16 in (8 mm)
Terminal screw torque
5 in-lb (0.5 N·m)

Connect Lutron Sivoia QS window treatments or lighting devices

PDF page 1 of 045528, opens in a new tab
Output terminal blocks
10 x 4-pin (COM, V+, MUX, MUX), packed separately
Strip length
1/4 in (6 mm)
Terminal screw torque
5 in-lb (0.5 N·m)
Wiring class
NEC Class 2 / PELV
Power (V+ and COM)
12 AWG to 18 AWG (4.0 mm² to 1.0 mm²)
Communication (MUX and MUX)
22 AWG (0.5 mm²) twisted, shielded pair
QS link wiring on panel outputs, all outputs combined
2000 ft (610 m) maximum
Wiring on the 3-pin communication link
2000 ft (610 m) maximum
Devices per QS link, outputs and communication link combined
100 maximum
None + up to 8 PDUs per output
2000 ft (610 m) on 12 AWG (4.0 mm²); 1000 ft (305 m) on 16 AWG (1.5 mm²); 600 ft (183 m) on 18 AWG (1.0 mm²)
1 shade or drapery drive + up to 1 PDU per output
500 ft (152 m) on 12 AWG (4.0 mm²); 200 ft (61 m) on 16 AWG (1.5 mm²); 125 ft (38 m) on 18 AWG (1.0 mm²)
2 Roller 64, 30 sq ft (2.75 sq m) or less each, + up to 1 PDU
200 ft (61 m) on 12 AWG (4.0 mm²); 75 ft (23 m) on 16 AWG (1.5 mm²); 50 ft (15 m) on 18 AWG (1.0 mm²)
3 Roller 64, 20 sq ft (1.80 sq m) or less each, + up to 1 PDU
200 ft (61 m) on 12 AWG (4.0 mm²); 75 ft (23 m) on 16 AWG (1.5 mm²); 50 ft (15 m) on 18 AWG (1.0 mm²)
2 Roller 100, 50 sq ft (4.60 sq m) or less each, + up to 1 PDU
200 ft (61 m) on 12 AWG (4.0 mm²); 75 ft (23 m) on 16 AWG (1.5 mm²); 50 ft (15 m) on 18 AWG (1.0 mm²)

Connect Multiple Smart Panels and other QS Devices

PDF page 1 of 045528, opens in a new tab
Link terminal blocks
2 x 3-pin (COM, MUX, MUX), packed separately
Strip length
1/4 in (6 mm)
Terminal screw torque
5 in-lb (0.5 N·m)

Monitor, Verify, Diagnose Operation

PDF page 1 of 045528, opens in a new tab
Link diagnostic mode time-out
10 minutes
Button hold to enter or exit link diagnostic mode
5 seconds on All Shades Open

Installation walk-through for 045528

Lutron document 045528 gives nine steps, in the document's order, after the fixings it lists.

The clearance, the check and the warning under a step are the document's own.

Fixings

  • Fasteners suited to the surface, rated for 50 lb (23 kg), not provided
  • Strain relief device for each knockout used (not included)
  • Ten 4-pin output terminal blocks (provided, packed separately)
  • Two 3-pin link terminal blocks (provided, packed separately)
  1. Prepare the panel

    Loosen the four front cover screws, slide the cover upward and lift it off. Take out the two line voltage shield screws and lift the shield out of the enclosure.

  2. Mount the panel

    Pick a spot that stays accessible; no mounting hardware is supplied. Surface mount on the three keyholes in the back, or recess mount on a horizontal board between the studs.

    A recess mount fixes to the right-hand stud and the board.

    Clearance: Fasteners rated for a 50 lb (23 kg) load

  3. Bring in the line feed

    Remove a knockout near the input terminal blocks and fit a strain relief. Run the feed to the input terminals at the top left of the enclosure.

    Clearance: 10 AWG to 14 AWG (4.0 mm² to 2.5 mm²) feed; breaker 15 A minimum, 20 A maximum

    Warning: Risk of electric shock: switch the supply breaker off and lock it there before touching the terminal block.

  4. Connect line, neutral and ground

    Strip each conductor and insert line, neutral and ground in the order drawn. Tighten each screw with no insulation inside the terminal, then tighten the strain relief.

    Clearance: 5/16 in (8 mm) strip; 5 in-lb (0.5 N·m) torque

    Check: No insulation inside the terminal block.

  5. Refit the line voltage shield

    Put the shield back with its original screws so all line voltage wiring and connections sit behind it.

    Check: Every line voltage connection is enclosed behind the shield.

    Warning: Never energize or operate the panel without the line voltage shield in place.

  6. Connect the window treatments or lighting devices

    Lutron recommends making the last connection at the device after the panel is in. Run each device cable through a strain relief in a left-side knockout.

    Wire COM and V+ into a 4-pin block, adding MUX and MUX for wired communication. Then plug the block into an output.

    Clearance: 1/4 in (6 mm) strip; 5 in-lb (0.5 N·m) torque; run length within the output table

    Check: Shade limits and free travel checked right after power-up.

    Warning: Risk of electric shock and fire: never interconnect power output terminals.

  7. Link further panels and QS devices

    Run 3-conductor cable from the other panel or Sivoia QS device through a strain relief by the Link receptacles. Wire COM, MUX and MUX into a 3-pin block and plug it into a Link receptacle.

    Clearance: 1/4 in (6 mm) strip; 5 in-lb (0.5 N·m); 2000 ft (610 m) maximum on the 3-pin link

    Warning: Panels link only through the 3-pin communication link, never through the 4-pin outputs.

  8. Read the LEDs

    With power modules fitted, a link diagnostic LED on or flashing means devices are talking; off means not. An output LED on is normal, off means a short or a failed module, and flashing means an overload.

    Check: After clearing any fault, tap Clear Alerts to resume operation.

  9. Verify communication

    On All Shades Open, tap, hold 5 seconds, release, then tap and hold 5 seconds again. LED devices flash and motorized window treatments wiggle.

    The test times out after 10 minutes, or a 5-second hold exits.

    Check: Any device that does not react has its power and communication wiring checked.

Other warnings Lutron prints in 045528
  • All wiring and circuit protection to national and local electrical codes
  • Some sites need a readily accessible disconnect outside the panel
  • A qualified electrician must install the panel.
  • Indoor use only; the panel is not for phase-to-phase installations.
  • QS link wiring is NEC Class 2 / PELV; keep circuit separation and protection
  • V+ terminals must never be joined between outputs.

Requirements Lutron states in 045528

What the guide requires for a Sivoia QS shade before and during installation:

Input
120 V to 240 V AC, 50/60 Hz, 10 A. Not for phase-to-phase installations.
Per output
35 V DC, 143 mA, 5 W
Feed breaker
  • 15 A minimum, set by inrush current (16 A in some countries)
  • 20 A maximum
  • An external disconnect may be required
  • Qualified electrician only
Power modules
WIN-PS-5CC-R modules, fitted or replaced per Lutron installation guide 045550
Mounting
Surface mount on three keyholes with fasteners rated for 50 lb (23 kg), or recess mount between studs on a horizontal support board. Hardware not provided.
Line feed wiring
  • 10 AWG to 14 AWG (4.0 mm² to 2.5 mm²) through a strain relief
  • Strip 5/16 in (8 mm); terminal screws to 5 in-lb (0.5 N·m)
  • Line voltage shield refitted before energizing
Output wiring
  • Ten 4-pin blocks (COM, V+, MUX, MUX); strip 1/4 in (6 mm)
  • Power 12 AWG to 18 AWG (4.0 mm² to 1.0 mm²)
  • Communication 22 AWG (0.5 mm²) twisted shielded pair
  • Outputs never interconnected
QS link limits
  • NEC Class 2 / PELV
  • 2000 ft (610 m) across all panel outputs
  • 2000 ft (610 m) on the 3-pin link
  • 100 devices per QS link
  • Panels join only through the 3-pin link
Link diagnostic mode
  • All Shades Open: tap, hold 5 seconds, release, tap, hold 5 seconds
  • Devices flash or wiggle
  • Times out after 10 minutes
Connection order
Lutron recommends making the final connection at the device once the panel is installed. Then check shade limits and free travel straight after power-up.
Output status LED
  • On: normal
  • Off: a short circuit, or a failed power module
  • Flashing: an overload, cleared with Clear Alerts once the fault is fixed

Questions about document 045528

The answers come from Lutron document 045528 and New Way's record of it.

What is Lutron document 045528?

Lutron's one-page Sivoia QS smart panel installation guide, P/N 045528 revision E, dated 11/2017. The panel is a wall-mounted enclosure that holds WIN-PS-5CC-R power modules.

Which revision of 045528 is current?

Rev E, dated November 2017, is the revision Lutron publishes. New Way checked it against assets.lutron.com on 15 October 2026.

Which roller shades does 045528 cover?

Lutron Sivoia QS roller shades. Lutron document 045528 refers readers to document 045550.

How many shades can one smart panel output feed?

Lutron document 045528 feeds one drive plus up to 1 PDU per output, or shared outputs. Shared outputs take up to 1 PDU and shorter runs.

  • Two Roller 64 to 30 sq ft (2.75 sq m) each
  • Three Roller 64 to 20 sq ft (1.80 sq m) each
  • Two Roller 100 to 50 sq ft (4.60 sq m) each

What circuit breaker and feed wire does the panel need?

Lutron document 045528 calls for a feed breaker of 15 A minimum, set by inrush current, and 20 A maximum. Feed wire is 10 AWG to 14 AWG (4.0 mm² to 2.5 mm²), installed by a qualified electrician.

How are several smart panels linked together?

Lutron document 045528 links panels only through the 3-pin communication link (COM, MUX and MUX), never through the 4-pin outputs. That link carries at most 2000 ft (610 m), with 100 devices per QS link.

What does a flashing output LED mean?

Lutron document 045528 reads a flashing output LED as an overload, from a wiring error or a blocked shade. Once the fault is cleared, the Clear Alerts button resumes operation.

An LED that is off means a short circuit or a failed power module.

Can the smart panel be recessed into a stud wall?

Yes: Lutron document 045528 describes a recess mount on a horizontal board between the studs as a bottom support. The panel fixes to the right-hand stud and the board; no mounting hardware is supplied.

Ask about 045528

Other Sivoia QS installation guides

Installation guides for the same Sivoia QS system:

All 36 Sivoia QS installation guides

Documents used with 045528

Lutron document 045528 cites 045550, the WIN-PS-5CC-R installation guide, and 369405, the QS link power draw unit specification submittal. Lutron's plug-in and junction box supply guides are 045488 and 045604; the wiring guide and card are 045314 and 3671692.

Revisions of 045528

This page always shows the revision Lutron publishes today. Lutron replaces the file in place and does not keep earlier revisions online.

RevisionDateStatus
ENov 2017Current. The file on assets.lutron.com. Checked 15 Oct 2026.

Not covered in 045528, and what to read next

Lutron document 045528 does not cover fitting or replacing the WIN-PS-5CC-R power modules, or programming the shades.

  • Power modules: 045550, the WIN-PS-5CC-R installation guide
  • Programming: 045314, the Sivoia QS wiring and programming guide

Publisher and citation for document 045528

Lutron Electronics Co., Inc. publishes document 045528, Rev E, and serves it from assets.lutron.com. New Way hosts no copy and last checked the file there on 15 October 2026.

Lutron and Sivoia QS are trademarks of Lutron Electronics Co., Inc.

Reviewed by Edmond Hong, Technical Specialist, New Way.

Specifying Sivoia QS?

New Way supplies and installs Lutron Sivoia QS shading in Malaysia and Singapore. A New Way specifier can check your shade schedule and drawings before you submit.

The form opens with document 045528 filled in.