About document 045528
Lutron document 045528, Rev E of November 2017, is the Sivoia QS smart panel installation guide: feed breaker, mounting, line and output wiring, QS link rules, linking panels, and LED and button diagnostics.
What guide 045528 covers
Lutron document 045528 has these nine sections, all on its one page.
- Important notes
- Prepare the smart panel
- Mount the smart panel
- Connect line voltage
- Connect Sivoia QS window treatments or lighting devices
- QS link wiring rules and output capacity table
- Connect multiple smart panels and other QS devices
- Monitor, verify and diagnose operation
- FCC and IC notice and customer assistance
Specifications in 045528
Lutron document 045528 prints 32 values in the groups the document uses, each with the document's unit. A row names the catalog codes it applies to. The page link beside each group opens the PDF where the group starts.
- Input
- 120 V to 240 V~, 50/60 Hz, 10 AModels: QSPS-10PNL, QSPS-10PNL-NPM
- Per output
- 35 V DC, 143 mA, 5 WModels: QSPS-10PNL, QSPS-10PNL-NPM
Important Notes
PDF page 1 of 045528, opens in a new tab- Minimum feed circuit breaker
- 15 A, set by inrush current (16 A may suit some countries)
- Maximum feed circuit breaker
- 20 A
- Ambient operating temperature
- 32 °F to 104 °F (0 °C to 40 °C)
- Humidity
- 0 to 90%, non-condensing
- Use
- Indoor only; not for phase-to-phase installations
Mount the Smart Panel
PDF page 1 of 045528, opens in a new tab- Surface mount
- 3 keyholes; fasteners rated for a 50 lb (23 kg) load
- Figure 2a (surface mount), dimensions marked
- 4.75 in (121 mm); 0.75 in (22 mm); 1.50 in (38 mm); 6.00 in (152 mm); 1.77 in (45 mm)
- Figure 2b (recess mount), dimension marked
- 16.00 in (406 mm)
Connect Line Voltage
PDF page 1 of 045528, opens in a new tab- Feed wire
- 10 AWG to 14 AWG (4.0 mm² to 2.5 mm²)
- Strip length
- 5/16 in (8 mm)
- Terminal screw torque
- 5 in-lb (0.5 N·m)
Connect Lutron Sivoia QS window treatments or lighting devices
PDF page 1 of 045528, opens in a new tab- Output terminal blocks
- 10 x 4-pin (COM, V+, MUX, MUX), packed separately
- Strip length
- 1/4 in (6 mm)
- Terminal screw torque
- 5 in-lb (0.5 N·m)
Rules for QS Link Wiring
PDF page 1 of 045528, opens in a new tab- Wiring class
- NEC Class 2 / PELV
- Power (V+ and COM)
- 12 AWG to 18 AWG (4.0 mm² to 1.0 mm²)
- Communication (MUX and MUX)
- 22 AWG (0.5 mm²) twisted, shielded pair
- QS link wiring on panel outputs, all outputs combined
- 2000 ft (610 m) maximum
- Wiring on the 3-pin communication link
- 2000 ft (610 m) maximum
- Devices per QS link, outputs and communication link combined
- 100 maximum
- None + up to 8 PDUs per output
- 2000 ft (610 m) on 12 AWG (4.0 mm²); 1000 ft (305 m) on 16 AWG (1.5 mm²); 600 ft (183 m) on 18 AWG (1.0 mm²)
- 1 shade or drapery drive + up to 1 PDU per output
- 500 ft (152 m) on 12 AWG (4.0 mm²); 200 ft (61 m) on 16 AWG (1.5 mm²); 125 ft (38 m) on 18 AWG (1.0 mm²)
- 2 Roller 64, 30 sq ft (2.75 sq m) or less each, + up to 1 PDU
- 200 ft (61 m) on 12 AWG (4.0 mm²); 75 ft (23 m) on 16 AWG (1.5 mm²); 50 ft (15 m) on 18 AWG (1.0 mm²)
- 3 Roller 64, 20 sq ft (1.80 sq m) or less each, + up to 1 PDU
- 200 ft (61 m) on 12 AWG (4.0 mm²); 75 ft (23 m) on 16 AWG (1.5 mm²); 50 ft (15 m) on 18 AWG (1.0 mm²)
- 2 Roller 100, 50 sq ft (4.60 sq m) or less each, + up to 1 PDU
- 200 ft (61 m) on 12 AWG (4.0 mm²); 75 ft (23 m) on 16 AWG (1.5 mm²); 50 ft (15 m) on 18 AWG (1.0 mm²)
Connect Multiple Smart Panels and other QS Devices
PDF page 1 of 045528, opens in a new tab- Link terminal blocks
- 2 x 3-pin (COM, MUX, MUX), packed separately
- Strip length
- 1/4 in (6 mm)
- Terminal screw torque
- 5 in-lb (0.5 N·m)
Monitor, Verify, Diagnose Operation
PDF page 1 of 045528, opens in a new tab- Link diagnostic mode time-out
- 10 minutes
- Button hold to enter or exit link diagnostic mode
- 5 seconds on All Shades Open
Installation walk-through for 045528
Lutron document 045528 gives nine steps, in the document's order, after the fixings it lists.
The clearance, the check and the warning under a step are the document's own.
Fixings
- Fasteners suited to the surface, rated for 50 lb (23 kg), not provided
- Strain relief device for each knockout used (not included)
- Ten 4-pin output terminal blocks (provided, packed separately)
- Two 3-pin link terminal blocks (provided, packed separately)
Prepare the panel
Loosen the four front cover screws, slide the cover upward and lift it off. Take out the two line voltage shield screws and lift the shield out of the enclosure.
Mount the panel
Pick a spot that stays accessible; no mounting hardware is supplied. Surface mount on the three keyholes in the back, or recess mount on a horizontal board between the studs.
A recess mount fixes to the right-hand stud and the board.
Clearance: Fasteners rated for a 50 lb (23 kg) load
Bring in the line feed
Remove a knockout near the input terminal blocks and fit a strain relief. Run the feed to the input terminals at the top left of the enclosure.
Clearance: 10 AWG to 14 AWG (4.0 mm² to 2.5 mm²) feed; breaker 15 A minimum, 20 A maximum
Warning: Risk of electric shock: switch the supply breaker off and lock it there before touching the terminal block.
Connect line, neutral and ground
Strip each conductor and insert line, neutral and ground in the order drawn. Tighten each screw with no insulation inside the terminal, then tighten the strain relief.
Clearance: 5/16 in (8 mm) strip; 5 in-lb (0.5 N·m) torque
Check: No insulation inside the terminal block.
Refit the line voltage shield
Put the shield back with its original screws so all line voltage wiring and connections sit behind it.
Check: Every line voltage connection is enclosed behind the shield.
Warning: Never energize or operate the panel without the line voltage shield in place.
Connect the window treatments or lighting devices
Lutron recommends making the last connection at the device after the panel is in. Run each device cable through a strain relief in a left-side knockout.
Wire COM and V+ into a 4-pin block, adding MUX and MUX for wired communication. Then plug the block into an output.
Clearance: 1/4 in (6 mm) strip; 5 in-lb (0.5 N·m) torque; run length within the output table
Check: Shade limits and free travel checked right after power-up.
Warning: Risk of electric shock and fire: never interconnect power output terminals.
Link further panels and QS devices
Run 3-conductor cable from the other panel or Sivoia QS device through a strain relief by the Link receptacles. Wire COM, MUX and MUX into a 3-pin block and plug it into a Link receptacle.
Clearance: 1/4 in (6 mm) strip; 5 in-lb (0.5 N·m); 2000 ft (610 m) maximum on the 3-pin link
Warning: Panels link only through the 3-pin communication link, never through the 4-pin outputs.
Read the LEDs
With power modules fitted, a link diagnostic LED on or flashing means devices are talking; off means not. An output LED on is normal, off means a short or a failed module, and flashing means an overload.
Check: After clearing any fault, tap Clear Alerts to resume operation.
Verify communication
On All Shades Open, tap, hold 5 seconds, release, then tap and hold 5 seconds again. LED devices flash and motorized window treatments wiggle.
The test times out after 10 minutes, or a 5-second hold exits.
Check: Any device that does not react has its power and communication wiring checked.
Requirements Lutron states in 045528
What the guide requires for a Sivoia QS shade before and during installation:
- Input
- 120 V to 240 V AC, 50/60 Hz, 10 A. Not for phase-to-phase installations.
- Per output
- 35 V DC, 143 mA, 5 W
- Feed breaker
- 15 A minimum, set by inrush current (16 A in some countries)
- 20 A maximum
- An external disconnect may be required
- Qualified electrician only
- Power modules
- WIN-PS-5CC-R modules, fitted or replaced per Lutron installation guide 045550
- Mounting
- Surface mount on three keyholes with fasteners rated for 50 lb (23 kg), or recess mount between studs on a horizontal support board. Hardware not provided.
- Line feed wiring
- 10 AWG to 14 AWG (4.0 mm² to 2.5 mm²) through a strain relief
- Strip 5/16 in (8 mm); terminal screws to 5 in-lb (0.5 N·m)
- Line voltage shield refitted before energizing
- Output wiring
- Ten 4-pin blocks (COM, V+, MUX, MUX); strip 1/4 in (6 mm)
- Power 12 AWG to 18 AWG (4.0 mm² to 1.0 mm²)
- Communication 22 AWG (0.5 mm²) twisted shielded pair
- Outputs never interconnected
- QS link limits
- NEC Class 2 / PELV
- 2000 ft (610 m) across all panel outputs
- 2000 ft (610 m) on the 3-pin link
- 100 devices per QS link
- Panels join only through the 3-pin link
- Link diagnostic mode
- All Shades Open: tap, hold 5 seconds, release, tap, hold 5 seconds
- Devices flash or wiggle
- Times out after 10 minutes
- Connection order
- Lutron recommends making the final connection at the device once the panel is installed. Then check shade limits and free travel straight after power-up.
- Output status LED
- On: normal
- Off: a short circuit, or a failed power module
- Flashing: an overload, cleared with Clear Alerts once the fault is fixed
Questions about document 045528
The answers come from Lutron document 045528 and New Way's record of it.
What is Lutron document 045528?
Lutron's one-page Sivoia QS smart panel installation guide, P/N 045528 revision E, dated 11/2017. The panel is a wall-mounted enclosure that holds WIN-PS-5CC-R power modules.
Which revision of 045528 is current?
Rev E, dated November 2017, is the revision Lutron publishes. New Way checked it against assets.lutron.com on 15 October 2026.
Which roller shades does 045528 cover?
Lutron Sivoia QS roller shades. Lutron document 045528 refers readers to document 045550.
How many shades can one smart panel output feed?
Lutron document 045528 feeds one drive plus up to 1 PDU per output, or shared outputs. Shared outputs take up to 1 PDU and shorter runs.
- Two Roller 64 to 30 sq ft (2.75 sq m) each
- Three Roller 64 to 20 sq ft (1.80 sq m) each
- Two Roller 100 to 50 sq ft (4.60 sq m) each
What circuit breaker and feed wire does the panel need?
Lutron document 045528 calls for a feed breaker of 15 A minimum, set by inrush current, and 20 A maximum. Feed wire is 10 AWG to 14 AWG (4.0 mm² to 2.5 mm²), installed by a qualified electrician.
How are several smart panels linked together?
Lutron document 045528 links panels only through the 3-pin communication link (COM, MUX and MUX), never through the 4-pin outputs. That link carries at most 2000 ft (610 m), with 100 devices per QS link.
What does a flashing output LED mean?
Lutron document 045528 reads a flashing output LED as an overload, from a wiring error or a blocked shade. Once the fault is cleared, the Clear Alerts button resumes operation.
An LED that is off means a short circuit or a failed power module.
Can the smart panel be recessed into a stud wall?
Yes: Lutron document 045528 describes a recess mount on a horizontal board between the studs as a bottom support. The panel fixes to the right-hand stud and the board; no mounting hardware is supplied.
Other Sivoia QS installation guides
Installation guides for the same Sivoia QS system:
| Document | Drive class | Revision | Date |
|---|---|---|---|
| 045314Roller Shades Installation Guide | Roller 20 to 300 | B | Jun 2014 |
| 045488Roller Shades Installation Guide: QS Link Plug-In Power Supply, NEMA 5-15 Plug, 120 V to 240 V Input, 35 V Output | Roller 20 to 300 | B | Jul 2016 |
| 045604Roller Shades Installation Guide: QS Power Supply J-Box Mount | Roller 20 to 300 | A | |
| 3671692Roller Shades Installation Guide: Quick Programming Reference Card | Roller 20 to 300 | A | Jan 2010 |
Documents used with 045528
Lutron document 045528 cites 045550, the WIN-PS-5CC-R installation guide, and 369405, the QS link power draw unit specification submittal. Lutron's plug-in and junction box supply guides are 045488 and 045604; the wiring guide and card are 045314 and 3671692.
| Document | Type | Revision | Date |
|---|---|---|---|
| 085835Serena Open Roll Roller Shades Specification Submittal | Specification Submittal | A | Feb 2026 |
| 369612Pico Wireless Control Specification Submittal | Specification Submittal | Q | Jun 2025 |
| CAD Drawing: 30-Output Configurable Power Panel Enclosure (Power Modules Sold Separately), 35V Output, Elevation View (Front) | CAD Drawing | ||
| CAD Drawing: 30-Output Configurable Power Panel Enclosure (Power Modules Sold Separately), 35V Output, Plan View (Bottom) | CAD Drawing | ||
| 08533510-Output Smart Panel Specification Submittal | Specification Submittal | D | Apr 2020 |
| 08559230-Output Configurable Power Panel Enclosure (Power Modules sold separately), 35V Output Specification Submittal | Specification Submittal | B | Nov 2018 |
| Roller Shades Wiring Diagram: Multiple Shades per Single QS Smart Panel | Wiring Diagram | ||
| Roller Shades Wiring Diagram: One Shade per Single QS Smart Panel | Wiring Diagram | ||
| Revit Family: QS J-Box 35V Power Supply | Revit Family | ||
| Revit Family: QS Smart Power Panel, 30 Output | Revit Family |
Revisions of 045528
This page always shows the revision Lutron publishes today. Lutron replaces the file in place and does not keep earlier revisions online.
| Revision | Date | Status |
|---|---|---|
| E | Nov 2017 | Current. The file on assets.lutron.com. Checked 15 Oct 2026. |
Not covered in 045528, and what to read next
Lutron document 045528 does not cover fitting or replacing the WIN-PS-5CC-R power modules, or programming the shades.
- Power modules: 045550, the WIN-PS-5CC-R installation guide
- Programming: 045314, the Sivoia QS wiring and programming guide
Publisher and citation for document 045528
Lutron Electronics Co., Inc. publishes document 045528, Rev E, and serves it from assets.lutron.com. New Way hosts no copy and last checked the file there on 15 October 2026.
Lutron and Sivoia QS are trademarks of Lutron Electronics Co., Inc.
Reviewed by Edmond Hong, Technical Specialist, New Way.
Specifying Sivoia QS?
New Way supplies and installs Lutron Sivoia QS shading in Malaysia and Singapore. A New Way specifier can check your shade schedule and drawings before you submit.
The form opens with document 045528 filled in.